24 Volt Linear Power Supply Units - EN54 Compliance

RGL Electronics manufacture a range of Linear Power Supplies for the Fire industry that relates to the EN54 Power Supply standards for Fire Systems.

The design is a microprocessor based intelligent unit providing all the facilities that are required to meet the standards and offer the installer a range of options depending on load output and standby battery requirements.

MODEL SUPPLIED ALL MODELS
Regulated DC
Output
Full Current to Load
Mains LED GREEN
Fault LED RED
Charging LED YELLOW
Fault Relays See Below
Box Sizes To suit Battery Requirements
Note :

The table is for information only and much depends on the sytem battery standby requirements as per the EN54 standards. Contact RGL with your specific requirements to determine the correct model for your application.

The design offers a comprehensive fault diagnostics of the Power Supply, an LED indication plus alarm signals (through on board voltage free change-over contacts) are generated in the following instances:
  • Mains Fail
  • Fuse Blown
  • Battery Missing
  • Overload
  • Low voltage battery

In addition to the above the range offers the following features:

  • Low/High voltage indication (LED only).
  • High Load (LED only).
  • Front and Rear Tamper.
  • Over voltage protection.
  • Over current protection.
Features :
  • 27.6 v DC Regulated Output
  • Full Current to Load
  • Additional Battery Charging Current
  • Short Circuit protection
  • Mains Present Indicator
  • Fuse Blown Indicator
  • Battery Charging Indicator
  • Fault Relay
    • Mains Fail (Separate Alarm Relay Timed Delay).
    • Fuse Blown
    • Battery Missing
    • Overload
    • Low voltage battery
  • Over Discharge Protection
  • Over Current Protection
  • Over Voltage Protection
  • Mains transient protection
  • Battery current limiting protection circuit.
  • Range of Enclosures to suit Output & Battery requirements.
Technical Specification
MAINS INPUT 220 - 240V AC 50/60HZ
D/C OUTPUT Full Stated Load @ 27.6v DC excluding Battery Charging circuit
LOAD VOLT REGULATION 5% Maximum
OUTPUT RIPPLE < 5% OF THE NOMINAL DC OUTPUT VOLTAGE
ENVIRONMENT Ambient Temp -20 to + 40ºC Relative Humidity 10 to 90%
BATTERY 12 Volt Sealed lead acid maximum 2 x 7ah
DEEP DISCHARGE PROTECTION Disconnects battery from load when battery voltage drops below 20 volts.
FAULT INDICATOR L.E.D. (RED) & RELAY Mains Fail, Fuse Blown, Over Current, Low Battery Voltage & Battery Missing.